霍尼韦尔MCV2500
日期:2025-05-18 10:17
浏览次数:1448
摘要:
MCV2500 SERIES
2-WAY AND 3-WAYHYDRONIC VALVES
PRODUCTSPECIFICATION SHEET
APPLICATION
霍尼韦尔MCV2500
The MCV2500 serieshydronic valves are designed for
residential heatingand cooling applications.
The MCV2500 series2-position hydronic valves are
used in residentialand small commercial applications
to control the flowof hot and/or cold water. They
consist of actuatorand valve.
2-way valves aredesigned for ON-OFF "zone" control
of domesticsystems.
3-way valves can bepiped for mixing valve
applications tocontrol individual fan coil, baseboard
radiator indomestic central heating and/or cooling
systems.
2-way valves aresuitable from A to B, and 3-way
valves are formixing water from A or B to AB.
Depending on themodel selected they can be
controlled by a lowor line voltage SPST or SPDT
controller, such asa room thermostat, aquastat or flow
switch.
霍尼韦尔MCV2500
FEATURES
FEATURES
_2-way or 3-way body
_Control by a low or line voltage SPSTor SPDT
controller
_100~130 VAC or 200~240VAC actuatorsavailable
_1000mm lead wires
_Minimal actuator powerconsumption
_Pressure differential up to3.0bar
_1~90 °C fluidtemperature
_ 0~65 °C ambienttemperature
APPLICATION
The MCV2500 serieshydronic valves are designed for
residential heatingand cooling applications.
The MCV2500 series2-position hydronic valves are
used in residentialand small commercial applications
to control the flowof hot and/or cold water. They
consist of actuatorand valve.
2-way valves aredesigned for ON-OFF "zone" control
of domesticsystems.
3-way valves can bepiped for mixing valve
applications tocontrol individual fan coil, baseboard
radiator indomestic central heating and/or cooling
systems.
2-way valves aresuitable from A to B, and 3-way
valves are formixing water from A or B to AB.
Depending on themodel selected they can be
controlled by a lowor line voltage SPST or SPDT
controller, such asa room thermostat, aquastat or flow
switch.
Contents
Application………………………………………………… 1
Features…………………………………………………… 1
Specification………………………………………………… 2~3
Dimensions………………………………………………… 3
Installation…………………………………………………. 4
Wiring Diagram ………………………………………………4
MCV2500 SERIES HYDRONICVALVE
SPECIFICATION
Voltage : AC110/220V±10%,50/60Hz Pipe connection : PT
Colour-coded
label : Green, Black,White Maximum pressure : 16bar max.
Control
Performance : SPST/SPDTcontrol Electrical termination: with integral 1000mm lead-wire cable
Power
Consumption Ambient Temperature : 0 ~ 65 °C
: 6W at nominalvoltages
(during valve position changeonly) AmbientHumidity : 10 ~ 95%RH (no condensing
\
Operationallife
: Greater than60,000 cycles (all loads) for
motor and valvecontacts at 110/220V Storage temperature : -25 ~ 65 °C
Storage Humidity : 10 ~ 95%RH (nocondensing Valve SizePort Kv Max. operating differential pressure
2-way valve 3/4"A to B 3.0 3.0 bar
A to AB 3.0 3.0bar
3-way valve3/4"
B to AB 3.0 1.0bar
Table 2. Modelselection guide (1)
* MCV2510AJ =MC2510HE + MV2000AJ : AC110V, SPST, 1.5Nm, 3/4”, 2-way valve (withboth internal thread & PT fitting)
* MC25 : Actuatorfamily identifier
MCV2510AJ
* xx00 : AC220V,SPST
* xx01 : AC220V,SPDT
* xx10 : AC110V,SPST
* xx11 : AC110V,SPDT
* HE : 1.5Nmmotor
* J : 3/4”, Bothinternal thread
* MV2000 : valvefamily identifier
* A : 2-wayvalve
* M : 3-wayvalve
MC25 10 HE +MV2000 A J
Pipe connection :PT
Maximum pressure :16bar max.
Electricaltermination : with integral 1000mm lead-wire cable
Ambient Temperature: 0 ~ 65 °C
Ambient Humidity :10 ~ 95%RH (no condensing)
Storage temperature: -25 ~ 65 °C
Storage Humidity :10 ~ 95%RH (no condensing)
Voltage :AC110/220V±10%, 50/60Hz
Colour-coded
label : Green,Black, White
Control
Performance :SPST/SPDT control
Power
consumption
: 6W at nominalvoltages
(during valveposition change only)
Operationallife
: Greater than60,000 cycles (all loads) for
motor and valvecontacts at 110/220 V
Timing :20sec霍尼韦尔MCV2500
SPECIFICATION
Table 1. Kv &Differential Pressure
Valve Size PortKv Max. operating differential pressure
2-way valve 3/4"A to B 3.0 3.0 bar
A to AB 3.0 3.0bar
3-way valve3/4"
B to AB 3.0 1.0bar
霍尼韦尔MCV2500
Assembled
ModelOS#
Actuator
OS#
Valve
OS#
Specification
MCV2500AJ MC2500HEMV2000AJ AC220V, SPST, 1.5Nm, 3/4" 2-way valve, Both internalthread, PT fitting
MCV2501AJ MC2501HEMV2000AJ AC220V, SPDT, 1.5Nm, 3/4" 2-way valve, Both internalthread, PT fitting
MCV2510AJ MC2510HEMV2000AJ AC110V, SPST, 1.5Nm, 3/4" 2-way valve, Both internalthread, PT fitting
MCV2511AJ MC2511HEMV2000AJ AC110V, SPDT, 1.5Nm, 3/4" 2-way valve, Both internalthread, PT fitting
MCV2500MJ MC2500HEMV2000MJ AC220V, SPST, 1.5Nm, 3/4" 3-way valve, Both internalthread, PT fitting
MCV2501MJ MC2501HEMV2000MJ AC220V, SPDT, 1.5Nm, 3/4" 3-way valve, Both internalthread, PT fitting
MCV2510MJ MC2510HEMV2000MJ AC110V, SPST, 1.5Nm, 3/4" 3-way valve, Both internalthread, PT fitting
MCV2511MJ MC2511HEMV2000MJ AC110V, SPDT, 1.5Nm, 3/4" 3-way valve, Both internalthread, PT fitting
* ProductExamples
- MCV25xxAJ/MJ : Assembled model, Egg crate with 10 actuators and 10 valves
- MC25xxHE : Actuator only, Egg crate with 15 actuators
- MV2000AJ/MJ : Valves only, Egg crate with 30 pieces of 2-way/3-way valves
Fig.
霍尼韦尔MCV2500
1. The valve may beplumbed in any angle but
preferably not withthe actuator head below the
horizontal level ofthe valve body. Make sure there is
enough room aroundthe actuator head for servicing
orreplacement.
2. The valve bodycan be mounted directly onto the inlet
pipe. Mount themetal flange inserted in socket to
outlet pipe. Andthen tighten the socket enough to
make a seal. SeeFigure 1~2 for the detail dimension.
3. Mount the valvedirectly in the tube or pipe. Do not
grip actuator headwhile making and tightening
plumbingconnections. Either hold valve body in your
hand or attachadjustable spanner across the
hexagonal or flatfaces on the valve body.